Daikin Logomark technical Infomation
Field

To mount a compressor discharge sensor
LXE10E

    <Notice>
    Refrigerant capacity will be deficient if the DCHS is mounted incompletely.


    <Description>
    If the DCHS is mounted incompletely, the DCHS will detect the temperature
    low and the electric expansion valve will control the closing motion to
    protect the compressor.
    Therefore, amount of refrigerant circulation is reduced to minimum and
    deficient refrigeration capacity is occurred.

    Please confirm whether the DCHS and the thermal insulation tube are mounted completely.


Window Close