<Notice>
Refrigerant capacity will be deficient if the DCHS is mounted incompletely.
<Description>
If the DCHS is mounted incompletely, the DCHS will detect the temperature
low and the electric expansion valve will control the closing motion to
protect the compressor.
Therefore, amount of refrigerant circulation is reduced to minimum and
deficient refrigeration capacity is occurred.
Please confirm whether the DCHS and the thermal insulation tube are mounted completely.